This includes the Doorbell, Intercoms and Panic Alarm. (generaly anything powered by the transformer in the techbox)

Intercoms

Techbox:Show switch, intercom and LED

The handsets themselves are all hardwired together so that when any handsets are picked up at the same time users at each end may communicate. This means that without anyone calling anywhere else, a 4 way conversation is possible. When the phone is called, a loud buzz is produces by the speaker in the headset. If someone has the phone off the hook, you can’t call them (this is a good thing because then you can’t deafen the person holding the handset). Don't try and be funny by phoning yourself, those buttons are disabled so nothing will happen!

The phones are situated in 4 strategic locations around the building:

Number Location
1 Servery
2 Tech Box
3 Back Stage
4 Box Office
5 Spare/Unused

Back stage the intercom can be silenced by a small switch on the side of the unit. Regardless of whether it has been silenced or not, a small LED on the wall above the table will flash.

In the Techbox, the phones can be silenced using the show switch. When the show switch is activated, the LEDs along the front of the Techbox will flash GREEN instead of hearing a beep.

Panic Alarm

Panic alarm control and reset

There are two panic buttons, one in the box office and one in the café, all members of staff should know how to use them. When they are pressed a blue light flashes in the office, red LEDs flash in the tech box and if box office is pressed, a buzzer sounds in the café. They are reset by pressing the marked button behind the box office. If you press the button you should have several hefty people there in seconds, people are discouraged from playing with it. If you are in another part of the building and the alarm is set of, please send any available personnel the help the panicking FOH staff

TO RESET THE ALARM press the ‘reset’ button on top of the black box in the box office (shown on right)

The alarm is controlled from the black box, the signal and power is transferred through the same wires as the intercoms. The interface of the two systems is in the white box to the left of the black control box

This system has its history in Bedlam folklore but it was modified to include the "silent" running mode with the red and green flashing LEDs around Spring 2000 by the skill and design work of the legendary Steve "Box Office" Fryatt.

In the run up to fringe 2006 the panic alarm was also set up to supply power to the till and replace the tired batteries. However when the panic alarm in the box office has been activated, the system cuts the power and the till will not open

Panic.JPG

The alarm system is controlled from the black box in the box office. The panic alarm electronics are based around two relay switches this allows the system do be selective. If the box office alarm is triggered, an alarm is sounded in the café whilst cutting power to the box office till. These functions would not be desirable if the café alarm was triggered. The circuit diagram shown above represents one relay.

The pins 1 & 2 are used as the input to the relay. When there is no voltage difference between them, the pins 5 & 6 are connected to 3 & 4 respectfully. When there is a voltage over pins 1 & 2, pins 5 & 6 are connected to 7 & 8 respectfully.

Pin 5 is connected to 0V whilst pins 2 & 6 are connected to +12V this means that to cause the relay to close, pin 1 needs to be connected to 0V. This can be done by the trigger switch connecting pin 1 to 0V or by a feedback loop created when the switch is closed and pin 5 (0V) is connected to pin 7 which is hard wired to pin 1. To break the feedback loop, the reset switch is opened and the +12V power supply is interrupted.

Pin 8 is the alarm signal. When the alarm is activated, this line is set to +12V and triggers alarms in other parts of the building

Pin 3 is unused in both relays whilst pin 4 is only used in the box office relay. When the alarm is not activated, it is connected to 12V. This is used to supply power to the till. When the alarm is activated the power is no longer provided and so the till is effectively locked.

I hope this made some sense and helps the next poor bugger that tries to fix it

Doorbell

The doorbell on the side entrance is attached to an old fire alarm which makes it loud enough to be heard anywhere in the building. It can be changed to a quiet buzzer mode which is for dress runs however this is often ignored/not herd to change it to the quiet mode swap the red switch on the side of the cupboard on your right as you enter the side entrance (behind the door). The small silver switch at the bottom f the box allows the doorbell to remain active the whole time. It can be turned off for shows at a switch in the tech box.

Power and Cables

The systems are all powered by a 12V transformer (though I think it is currently running at 13.8V) sitting under the tech box desk far end, stage right (under lighting desk). The panic alarm and phones are almost two separate systems that meet in the tech box and use the same cabling to speak to the tech box and other parts of the building. The cabling system is based on bell wire (12 cores) though there is a small section in the servery that uses two small stretches of cat5 (8 cores) (this is because we couldn’t find any bell wire and currently the building has kilometres of cat5)

Cable map

Please note that the cables are of the age that make them brittle buggers and liable to snap at any movement. This also means that they have faded and as such identifying the colours is a pain. When two colours are listed, i.e. White/Blue this denotes White wire with Blue stripes.

Channel Name Bell Cat5 Phone
1-Serv Servery Green/White Green Black
2-TB Tech Box White/Green* White/Green D Brown
3-BS Back Stage Brown/White Brown L Brown
4-BO Box Office White/Brown White/Brown Purple
5-SP Spare Grey/White Orange Orange
6 - - - Yellow
7 - - - Peach
8 - - - White/Blue
9 - - - Grey
10 - - - Grey?
Incoming Call - - - White
Voice Phone Line Orange/White White/Orange Mint Green
+ +12V Red/Blue White/Blue Red
- 0V Blue/Purple Blue Blue
PANIC Panic Alarm Trigger White/Orange White/Orange# -

*The White/Green wire between BO and Serv has a break in it somewhere; this has been fixed by using the White/Grey wire over this section.

# This means that it is in the second cat5 cable (the one with the green tape on it)

Bedlam Wiring.gif

Junction box 1 is situated under the techbox just on the left as you enter the hole from stage right side (under light desk)

Junction box 2 is under the counter hatch